EM2800 Series Earth Resistance Online Detector


EM2800E Earth Resistance Online Detector
Product Series : Earth Resistance Online Monitoring Module
Main Features
Online monitoring of the loop earth resistance, earth current, metal loop connection resistance and grounding condition
Detector Structure: Split type
Sensor Open Jaw Size: Φ17mm
Working Power Supply: 9V DC~24V DC(external power supply)
Earth Resistance Range: 0.01Ω ~ 200Ω
Earth Current Range: 0.0mA~20A
RS485 Communication: Supports MODBUS-RTU communication protocol
4G Communication: Supports MQTT protocol (optional)
Alarm Function
Self-checking Function
Product Introduction
EM2800E Earth Resistance Online Detector is used for online monitoring of earth resistance, connection condition of gounding down lead, loop earth resistance, metal loop connection resistance and earth current. It is also known as earth resistance online tester and loop resistance online tester. The detector adopt split-type structure design. The sensors and controllers are installed independently so that it is convenient to observe earth resistance values and manage controllers, and is particularly suitable for users’ secondary development and integration. The detector adopts non-contact measurement technology, and the grounding down lead passes through the perforation of detector directly, will not affects the grounding lightning protection effect and the normal working of the equipment. The detector has multiple structures to adapt to different application scenarios, with IP65 protection level and supports outdoor installation and operation. It is widely applied to transmission line tower grounding, meteorological lightning protection grounding, petrochemical grounding, communication grounding, substation grounding, railway facility grounding, distribution box grounding, building and warehouse grounding, metal loop resistance testing, electrical equipment grounding, etc.
EM2800E Earth Resistance Online Detector consists of sensors and controllers. Sensors have closed-loop type and open-loop type. The open-loop type no need to disconnect gounding down lead, which is convenient and efficient. The detector can be installed and operated individually or integrated into a network system.
The detector is equipped with RS485 communication (supporting MODBUS-RTU protocol) or optional 4G communication (supporting MQTT protocol). An upper computer network monitoring system or 4G network monitoring system can be established via the EM2600 low-power data acquisition tester. Users can adopt our company’s EM2800-MT IoT Earth Resistance Online Monitoring System Software to conduct real-time monitoring and recording of parameters such as earth resistance values, set alarm thresholds and check alarm information through the system background. The background is equipped with functions including account management, information management, area management and equipment management.
The detector can be powered externally or by the optional EM2600 low-power data acquisition unit. The data acquisition tester adopt low-power design with built-in large-capacity lithium thionyl chloride batteries, solving the problem of inconvenient on-site power supply, with a battery life up to 3 to 5 years.
ETCRMETER is a high-end brand of ETCR. All products are manufactured by ETCR, which also provides technical support and after-sales service.
Product Features
1. The detector adopt split-type structure design so that it is convenient to observe earth resistance values and centralize management controllers.
2. Provide sensors and PCB modules to facilitate secondary development of online grounding resistance monitoring products.
3. Non-contact measurement technology, safe and reliable, easy to installation. The grounding down lead passes through the perforation of detector directly, will not affects the grounding lightning protection effect and the normal working of the equipment.
4. EM2800E sensors are compact in size, internally resin-potted, structurally robust, waterproof and dustproof for all-weather operation, making them particularly suitable for installation in narrow spaces.
5. With self-checking function, which enables remote detection whether the detector is working properly via protocol.
6. With line resistance elimination function, which can reduce the influence of line resistance on measurement errors.
7. Equipped with RS485 (support MODBUS-RTU communication protocol) or 4G communication module (optional) , connected with the user computer to remote real-time monitoring.
Technical Parameters
| Specification Name | Parameters Description |
| Functions | Online monitoring of loop earth resistance, metal loop connection resistance, grounding condition, and earth current |
| Power Supply | 9V DC ~ 24V DC (User external power supply or equipped with a low-power communication module) |
| LCD Display | 4-digit LCD, 47mm × 28.5mm |
| Earth Resistance Measurement | Range: 0.01Ω ~ 200Ω; Resolution: 0.001Ω; Accuracy: ± 2%rdg ± 3dgt |
| Earth Current Measurement | Range: AC 0.0mA ~ 20A; Resolution: 0.1mA; Accuracy: ± 2%rdg ± 5dgt |
| Shift | Fully automatic shifting |
| Overrange Indication | When resistance > 200Ω; current > 20A, “OL” displayed. |
| Power & Communication Wire Identification | Red: Power input positive ; Black: Power input negative Green: RS485 signal positive; Yellow: RS485 signal negative White: Shield ground (power input ground and shield ground can be short-circuited connect) |
| Uploaded Data | Earth resistance value, earth current value, alarm threshold |
| Network Points | Wired network: 1 ~ 250 grounding points, expandable Wireless network: 60000 grounding points, expandable |
| Communication Distance | Wired network: Approx. 1000m, expandable Wireless network: Unlimited |
| Alarm Indication | Audible & visual alarm + LCD display |
| Alarm Setting | Detector panel button setting, background setting |
| Ground Wire Interference Current | Avoide |
| External Magnetic Field | < 40A/m |
| External Electric Field | < 1V/m |
| Single Measurement Time | Approx. 0.5s |
| Working Current | 12VDC 50mA Max (4G version: 12VDC 150mA Max) |
| Protection Level | IP65 |
| RS485 Communication | Supports ModBus protocol |
| Normal 4G Version (Optional) | LTE-FDD B1 / B3 / B5 / B8 LTE-TDD B34 / B38 / B39 / B40 / B41 |
| Global 4G Version (Optional) | LTE-FDD;LTE-TDD B38 / B39 / B40 / B41 |
| Sensor Open Jaw Size | Φ17mm |
| Sensor Dimensions | 76mm × 60mm × 38mm |
| Controler Dimensions | 118mm × 112mm × 46mm |
| Weight | Approx. 430g |
| Working Temperature & Humidity | – 20℃ ~ 55℃;20%RH ~ 90%RH |