ETCR Meter Indonesia

Grounding Pile Type Earth Online Detector

EM2900/EM2900B/EM3350 Earth Resistance Online Detector

EM2900 Earth Resistance Online Detector
EM2900B Earth Resistance Online Detector
EM3350 Large Grounding Network Earth Resistance OnLine Monitor

EM2900B Earth Resistance Online Detector

 

Product Series : Grounding Pile Type Earth Online Detector

 

Main Features

 

Online monitoring of the earth resistance, earth voltage.
Earth Resistance Measurement Range: 0.01Ω ~ 2000Ω
Earth Voltage Measurement Range: AC 0V ~ 600V
Communication Mode: RS485 communication
Alarm Function: Setting alarm threshold
Setting Monitoring Interval

Product Introduction

 

EM2900B Earth Resistance Online Detector is also known as earth resistance remote online tester, contact type earth resistance online detector, which is used for remote online monitoring the earth resistance and earth voltage. The detector adopt with simple two-wire method or precision three-wire method to test earth resistance, and adopt the average value rectifier method to test the earth voltage and online real-time monitoring. The detector supports RS485 and 4G communication. Users can conduct secondary development and set up  network to realize remote multi-point online monitoring according to the provided MODBUS communication protocol. It is suitable for power facility grounding, highway equipment grounding, meteorological lightning protection grounding, communication base station grounding, railway facility grounding, construction warehouse grounding and electrical equipment grounding, etc.
EM2900B Earth Resistance Online Detector equip with LCD displayer, which can view the earth resistance value on site, set the alarm threshold value through the detector button, set the monitoring interval time, and with audible and visible alarm indication.The detector equipped with DIN rail mounting structure, which is particularly convenient to installation.
ETCRMETER is a high-end brand of ETCR. All products are manufactured by ETCR, which also provides technical support and after-sales service. 

Product Features
1. The detector adopt with simple two-wire method or precision three-wire method to test the earth resistance, and adopt average rectifier method to test the earth voltage.
2. RS485 communication and 4G communication function
3. Setting alarm threshold
4. Setting monitoring interval time
5. The detector equipped with DIN rail mounting structure, which is particularly convenient to installation.
  

Technical Parameters

1.Measurement Range & Accuracy

Measurement ModeMeasure RangeAccuracyResolution
Earth Resistance0.01Ω~20Ω±2%rdg±3dgt (Auxiliary earth resistance: 100Ω ± 5%, earth voltage: < 10V)0.01Ω
0.1Ω~200Ω0.1Ω
1Ω~2000Ω1Ω
Earth Voltage0~600V AC± 2%rdg ± 3dgt1V

2.Technical Specification

Specification NameParameters Description
Power Supply

Standard: 12V ~ 24V (±1V DC), 400mA Max. (external supply)

Display Mode4 digit LCD display
LCD Size47mm × 28.5mm
Measure ModePrecise 3-wire measurement, simple 2-wire measurement
Measure Method

Earth resistance: Rated current change-pole method, measured current 11mA Max, 128Hz;

Earth voltage: average value rectification method
Earth Resistance Range0.01Ω~2000Ω
Earth Voltage RangeAC 0V~600V
Data ModeAverage
Measurement IndicationLCD countdown indication during measurement
Measurement Time

Earth voltage: approx. 2 times/second;
Earth resistance: approx. 30 second/time

Measurement TimesAbove 10000 times
Line VoltageMeasuring earth voltage: below AC 600V
Detector InterfacePluggable terminal blocks: 9 pin terminal
Communication ModeRS485; 4G
ShiftAutomatically
Data Storage99 groups , flash display” FULL” symbol indicate storage is full
Monitoring Interval TimeSetting range of automatic monitoring interval time: 1 ~ 999 h
Data AccessData access function: “READ” symbol display
Power ConsumptionStandby: 25mA Max, Measurement: 400mA Max
Alarm IndicationAudible & visible alarm
Alarm SettingDetector panel button setting or background setting
Alarm Threshold Setting Resistance: 0Ω~2000Ω
Low Power Supply Voltage IndicationWhen the power supply voltage drops below 11V, a low voltage symbol will be displayed to alarm the user to replace the power supply.
Detector Dimension130mm×90mm×54mm
WeightApprox. 380g
Overload ProtectionWhen measurement earth resistance: between E-P, E-C each interfaces AC 280V/3 second
Insulation ResistanceAbove 10MΩ (500V between the circuit and the housing)
Withstand VoltageAC 3700V/rms (between the circuit and the housing)
Electromagnetic PropertyIEC61010-4-3,Wireless frequency electromagnetic field ≤1V/m
Safe StandardIEC61010-1, IEC1010-2-31, IEC61557-1,5, IEC60529(IP54), pollution degree 2, CAT Ⅲ 300V
Working Temperature & Humidity– 10℃~40℃;below 80%RH
Storage Temperature & Humidity– 20℃~60℃;below 70%RH
Exit mobile version