EM2840 Series Lightning Current/Earth Online Detector

EM2840T Lightning Current/Earth Online Detector
Product Series : Lightning Current/Earth Online Detector
Main Features
SPD alarm action monitoring, including SPD alarm action time, lightning strike count, lightning current amplitude, earth resistance, earth current monitoring
Detector Structure: Separate type
Lightning Current CT Size: 120mm
Maximum Lightning Current Measurement Amplitude: 100KA
Minimum Lightning Current Measurement Amplitude: 2.5%FS
SPD Alarm Signal Monitoring Channels: 1
Earth Resistance Range: 0.01Ω~200Ω
Earth Current Range: AC 0.0mA~20A
RS485 Communication: Supports Modbus protocol
4G Communication (Optional)
Product Introduction
EM2840T Lightning Current/Earth Online Detector is installed on the earth down lead, which can monitor SPD alarm actions and time, lightning strike counts and amplitude in real time and accurately. The SPD alarm function is suitable for SPD devices with dry contact output, which can timely and rapidly monitor SPD operation status. The detector also measures earth resistance and earth current in real time.
EM2840T Lightning Current/Earth Online Detector consists of controller, sensor and mounting hardware. EM2700T monitor is integrated structure with combined sensor and controller. The detector has RS485 communication interface (supports MODBUS‑RTU protocol) or optional 4G communication module (supports MQTT protocol) and realizes remote online monitoring by upper computer software or background system. Users can use our company’s RS485 earth resistance online monitoring upper computer software or 4G wireless earth resistance online monitoring background to realize remote real‑time monitoring of earth conditions.
ETCRMETER is a high-end brand of ETCR. All products are manufactured by ETCR, which also provides technical support and after-sales service.
Product Features
1. The detector can monitor and collect SPD alarm signals.
2. Monitors earth resistance, earth current, and amplitude, polarity and occurrence time of lightning current.
3. Equipped with display screen for real‑time observation of measured earth resistance and earth current values.
4. With RS485 communication or 4G communication(optional) to realize remote monitoring.
5. The sensor housing is made of 304 stainless steel, making it sturdy, durable, impact-resistant, and resistant to high and low temperatures for all-weather use.
Technical Parameters
| Specification Name | Parameters Description |
| Functions | SPD alarm action monitoring, including SPD alarm action time, lightning strike count, lightning current amplitude, earth resistance, earth current monitoring |
| Power Supply | DC 9V~24V external power supply |
| Display Screen | 47mm × 28.5mm |
| Earth Resistance Measurement | Range: 0.01Ω~200Ω |
| Resolution: 0.001Ω | |
| Accuracy: ± 2%rdg ± 3dgt | |
| Earth Current Measurement | Range: AC 0.0mA~20A |
| Resolution: 0.1mA | |
| Accuracy: ± 2%rdg ± 5dgt | |
| Lightning Current Measurement | Max. measurement amplitude: 100kA(Customizable) |
| Min. measurement amplitude: 2.5%FS | |
| Accuracy: ±(10%rdg+1 %*Fs) | |
| SPD Alarm Channel | 1 |
| Alarm Time | Year, Month, Day, Hour, Minute, Second |
| Communication Mode | RS485 (Supports Modbus Protocol), 4G (Optional) |
| Upload Data | Lightning strikes counts, Lightning amplitude and time, Earth resistance value, Earth current value |
| Shift | Fully Automatic shifting |
| Overflow Indication | When resistance value > 200Ω; current value > 20A, display “OL” symbol. |
| Power and Communication Cable Wiring Labels | Red—Power input positive; |
| Network Count | Wired network: 1 ~ 250 earth points, expandable Wireless network: 60,000 earth points, expandable |
| Communication Distance | Wired network: Approx. 1000 meters, expandable Wireless network: Unlimited |
| Alarm Indication | Audible & visual alarm and LCD display |
| Alarm Setting | Setting with panel buttons, background setting |
| Sensor Opening Size | 53mm x 20mm |
| Earth Interference Current | Avoid |
| Single Measurement Time | Approx. 0.5s |
| Working Current | 12VDC 50mA Max. (12VDC 150mA Max. for 4G version) |
| Protection Level | IP66 |
| Monitor Dimensions | Controller: 118mm x 112mm x 46mm Sensor: 119mm x 75mm x 109mm |
| Weight | Approx. 1275g |
| Working Temperature & Humidity | – 20℃~55℃;20%RH~90%RH |