ETCR Meter Indonesia

Touch screen Power Quality Analyzer

EM5230/EM5230A Power Quality Analyzer

EM5230 Power Quality Analyzer

Product Series : Touch screen Power Quality Analyzer

Main Features

Comprehensively analyze and diagnose three-phase power parameters, providing complete power quality information
4-channel current & 3-channel voltage measurement
DC current & voltage measurement
Transient Recording
Screenshot Recording
Trend Chart Recording
Waveform Recording
TF Memory Card
Touch Color Screen
USB Communication Interface
Rechargeable Lithium Battery

Product Introduction

 

EM5230 Power Quality Analyzer is a high-precision comprehensive testing instrument meticulously developed by our company, specifically designed for on-site testing of three-phase power quality. The instrument features intelligence, complete functions, simple human-machine operation, and a bilingual (Chinese and English) operation interface. The instrument adopts a 7-inch touch color screen, is small in size, light in weight and easy to carry. It can be equipped with multiple types of current clamps. The instrument can simultaneously measure 4 channels of current (ABC three-phase and neutral line current), 3 channels of voltage, three-phase unbalance degree, active power, reactive power, apparent power, harmonic ratio, total harmonic distortion degree, etc. Display real-time waveforms and phasor diagrams of current and voltage; Dynamic capture of instantaneous changes in voltage and current, monitoring of starting current, monitoring of various power parameters and generating alarm lists, long-term recording of test data and generation of trend curve graphs, and other functions.
In current power applications, faults caused by an increasing number of large-scale electrical equipment and increasingly complex power grid systems are becoming more and more complex and difficult to troubleshoot. Moreover, due to the development of various industries, the requirements for power quality in power grids are also getting higher and higher. Therefore, we provide this method that can more quickly and accurately eliminate faults in complex power systems. Measurement and analysis instruments for more comprehensive and systematic monitoring and maintenance of power quality parameters. The EM5230 Power Quality Analyzer features a 7-inch touch color screen display, which uses different colors to distinguish and show the parameters, waveform diagrams, vector diagrams, and harmonic ratio diagrams of each phase, enabling users to understand the status of power grid parameters more efficiently and intuitively. The stored data is uploaded to the computer through the USB communication interface and the upper computer software for further data analysis. The power quality analyzer, also known as the intelligent three-phase power quality analyzer, multi-functional power quality analyzer, three-phase power quality analyzer, etc., also has the functions of harmonic analyzers, phase volt-ampere meters, power parameter testers and other instruments. It is applicable to power, petrochemical, metallurgy, railway, industrial and mining enterprises, scientific research institutions and universities, metrology departments, etc. It is especially suitable for comprehensive analysis and diagnosis of all electrical parameters such as voltage, current, power, energy, harmonics and phase.
ETCRMETER is a high-end brand of ETCR. All products are manufactured by ETCR, which also provides technical support and after-sales service.

Product Functions
1. Real-time waveform display (3-channel voltage / 4-channel current)
2. True RMS voltage and current
3. Phasor diagram display
4. Harmonic measurement up to the 51st harmonic
5. Harmonic content bar chart6. Total Harmonic Distortion (THD)
7. Active/reactive/apparent power (per phase and total)
8. Voltage/current/power trend chart9. Three-phase unbalance measurement
10. Waveform and parameter recording
11. Screenshot saving
12. Touchscreen operation
13. Voltage flicker, sag/swell capture
14. Inrush current and surge monitoring
15. USB PC communication
16. Wiring and grid configuration
17. Current clamp & voltage ratio selection
18. One-key phase volt-ampere, ratio test, DC test
19. Energy calculation
20. DC voltage, current & power measurement
21. The stored data can be exported into analysis reports in accordance with national standards

 

Technical Parameters

1. Reference & Operating Conditions

Influence QuantityTest ItemReference ConditionWorking Condition
Environment TemperatureAll Parameters(23±2)℃-10℃~40℃
Relative HumidityAll Parameters40%~60%<80%RH
VoltageTrue RMS Voltage(220±1%)V0.001V~1000V
CurrentTrue RMS Current(5±1%)A10mA~6000A
Grid FrequencyAll Parameters50Hz±0.1Hz40Hz~70Hz
HarmonicsAll Parameters<0.1%0.0%~100%
Voltage UnbalanceAll Parameters<10%0.0%~100%
Operating VoltageAll ParametersDC7.4V±0.1VDC 6.8V~8.4V
External E/M FieldAll ParametersAvoided
Conductor PositionCurrent-related TestsAt geometric center of clamp jaw

2. Measurement Accuracy

Measurement ItemMeasuring RangeDisplay ResolutionMax Error
Frequency40Hz~70Hz0.001Hz±0.01Hz
Voltage True RMS0.001V~600V0.001V±0.5%rdg±0.1%fs
DC Voltage0.1V~600V0.1V±0.5%rdg
Current True RMS0.01A~6000A0.001A±0.5%rdg
DC Current0.1A~1000A0.1A±0.5%rdg
Active Power0.001W~6000kW0.001W±(1%rdg+3dgt) (Cosφ≥0.8); ±(1.5%rdg+10dgt) (0.2≤Cosφ<0.8)
Reactive Power0.001VAR~6000kVAR0.001VAR±(1%rdg+3dgt) (Sinφ≥0.5); ±(1.5%rdg+10dgt) (0.2≤Sinφ<0.5)
Apparent Power0.001VA~6000kVA0.001VA±(1%rdg+3dgt)
Power Factor-1.000~1.0000.001±(1.5%rdg+3dgt) (Cosφ≥0.5); ±(1.5%rdg+10dgt) (0.2≤Cosφ<0.5)
Active Energy0.001kWh~9999.999MWh0.001kWh±(1%rdg+3dgt) (Cosφ≥0.8); ±(1.5%rdg+10dgt) (0.2≤Cosφ<0.8)
Reactive Energy (Inductive & Capacitive)0.001kVARh~9999.999MVARh0.001kVARh±(1%rdg+3dgt) (Sinφ≥0.5); ±(1.5%rdg+10dgt) (0.2≤Sinφ<0.5)
Apparent Energy0.001kVAh~9999.999MVAh0.001kVAh±(1%rdg+3dgt)
Voltage Harmonic Ratio (2nd–51st, Vrms>50V)0.0%~99.9%0.001%±(1%rdg+5dgt) (2nd–20th); ±(1%rdg+10dgt) (21st–30th); ±(1%rdg+15dgt) (31st–51st)
Voltage Harmonic Angle (Vrms>50V)0°~360°0.001°±3° (2nd–25th); ±10° (26th–51st)
Current Harmonic Ratio (2nd–51st, Arms>I range÷100)0.0%~99.9%0.001%±(1%rdg+5dgt) (2nd–20th); ±(1%rdg+10dgt) (21st–30th); ±(1%rdg+15dgt) (31st–51st)
Current Harmonic Angle (Arms>I range÷100)0°~360°0.001°±3° (2nd–25th); ±10° (26th–51st)
Total Harmonic Rate (THD/THD-F ≤50)0.0%~99.9%0.001%±(1%rdg+10dgt)
Distortion Factor (DF/THD-R ≤50)0.0%~99.9%0.001%±(1%rdg+10dgt)
Three-phase Unbalance0.0%~100%0.01%±1%

3. Current Clamp Characteristics

Current Clamp TypeTrue RMS CurrentMax ResolutionMax Error (True RMS)Max Phase Error
008B10mA~10.0A1mA±(1%rdg+0.05%fs)±2°
032B0.10A~100A1mA±(1%rdg+0.05%fs)±2°
050B1.0A~1000A1mA±(2%rdg+0.05%fs)±2°
300FA10.0A~6000A1mA±(1%rdg+0.05%fs)±2°
035AD0.1A~1000A0.1A±(3%rdg+0.05%fs)–

4. General Specifications

Specification NameParameters Description
Power SupplyDC7.4V 5200mAh rechargeable lithium battery, external charger
Battery IndicatorWhen the battery level is too low, the instrument will automatically shut down
Working CurrentApprox. 490mA
Clamp Jaw Sizes 

008B: Φ8mm (Optional);
032B: 32mm×40mm (Optional);
050B: Φ50mm (Optional);
300FA: Φ300mm (Optional); 
035AD: Φ30mm×35mm (Optional)

Dimensions240mm×170mm×68mm
Display7-inch touch color screen
Channels3-channel voltage, 4-channel current
AC Voltage Range0.001V~1000V
DC Voltage Range0.1V~1000V
Current008B: Φ8mm (Optional);
032B: 32mm×40mm (Optional);
050B: AC 1A~1000A (Optional);
300FA: AC 10A~6000A (Optional); 
035AD: DC 0.1A~1000A (Optional)
Frequency40Hz~70Hz
Harmonics2~51 times harmonics
Total Harmonic Distortion2~51 times harmonics (per phase)
Three-phase UnbalanceSupported
Communication InterfaceUSB
Menu LanguageChinese/English switchable
Auto Power OffDisabled during recording;

If the recording function is not enabled, it can automatically shut down after the set 15 minutes, 30 minutes or 60 minutes.

Weight
Host: approx. 1240g (with battery); 
008B current clamp: approx. 180g×4; (Optional)

032B current clamp: approx. 248g×4; (Optiona)

050B current clamp: approx. 520g×4; (Optional)

300FA current clamp: approx. 140g×4; (Optional)

035AD current clamp: approx. 240g×4; (Optional)
Attachment weight: approx. 3.34kg (accessories only);
Total weight: approx. 10.2kg(including packaging, complete set of current clamps and accessories)
Memory Card8GB TF card (expandable to 32GB)
Voltage Test Lead3m
Current Clamp Lead2m
Working Temperature & Humidity-10℃~40℃, ≤80%RH
Storage Temperature & Humidity-10℃~60℃, ≤70%RH
Input Impedance1MΩ for voltage input
Withstand Voltage3700V/50Hz AC for 1 minute
Insulation≥10MΩ between circuit and housing
StructureDouble insulation with anti-vibration sheath
Safety StandardsIEC 61010 1000V Cat III / 600V CAT IV, IEC61010-031, IEC61326, Pollution Degree 2

Model Comparison

Product ModelMeasurement ChannelsCurrent RangeVoltage RangeHarmonics

EM5000

4-channel current 

4-channel voltage

AC 0.01A~6000A1.0V ~ 2000V0 ~ 50 

EM5230A

4-channel current 

3-channel voltage

AC 0.01A~6000A1.0V ~ 600V2 ~ 51

EM5230
4-channel current 

3-channel voltage

AC 0.01A~6000A

DC 0.1A~1000A

AC/DC 1.0V~1000V2 ~ 51
Exit mobile version