Menu

Earth Resistance Tester, Earth Resistance/Lightning Strike Current Online Detector, High Voltage Insulation Resistance Tester, High Voltage Electroscope/Approach Electric Alarm.......

  • Home |
  • Phase Change Switch Type Three Phase Unbalance Correction Device

Phase Change Switch Type Three Phase Unbalance Correction Device

EM5500 Phase Change Switch Type Three Phase Unbalance Correction Device

EM5500 Phase Change Switch Type Three Phase Unbalance Correction Device

 

Product Series : Phase-change Switch Type Three-phase Unbalance Correction Device

Main Features :

This is a real-time, intelligent automatic load control system that performs on-load phase-shifting for single-phase loads, effectively resolving three-phase imbalance issues in low-voltage distribution networks.
Phase-Changing Time: 0ms
Rated Voltage: 380V/220V
Rated Current: 120A
Communication Method: LORA, RS485, 4G, Bluetooth

Product Introduction

 

The EM5500 Phase-Changing Switch Three Phase Unbalance Device, also known as an intelligent load dispatch system or a three-phase load imbalance correction device for transformer substations, is a real-time, intelligent automatic load control system that performs on-load phase-shifting dispatch of single-phase loads, effectively resolving three-phase imbalance issues in low-voltage distribution networks.
The EM5500 Phase-Changing Switch Three Phase imbalance correction device consists of a main controller and phase-shifting switches. The main controller collects real-time load data from the transformer substation; analyzes the load voltage and current of each phase-shifting switch; and generates and transmits commands to the phase-shifting switches. The phase-shifting switches receive and execute the commands from the main controller. Communication between the main controller and the phase-shifting switches is achieved via LoRa wireless communication or RS485 communication.
To manage a distribution transformer district, one main controller and several phase-shifting switches must be installed, depending on the transformer’s capacity and the severity of the imbalance. The phase-shifting switches receive commands from the main controller to shift single-phase loads between the three phases. This switching process occurs without interrupting power supply and does not affect users’ electricity consumption. This effectively resolves the issue of three-phase load imbalance in the distribution network.
ETCRMETER is a high-end brand of ETCR. All products are manufactured by ETCR, which also provides technical support and after-sales service.

Product Features
1. Unique 0-millisecond seamless phase-switching technology ensures uninterrupted power supply during phase switching under load, with no voltage sags or inrush currents, and no impact on sensitive loads; interphase interlocking eliminates the risk of interphase disconnections. The phase-switching time is 0 milliseconds, and the switching time is precisely controllable. The switching process is performed by power electronic devices, producing no arcing; after switching, a permanent magnet switch maintains a steady state with no power loss.
2. The commutation process is free of inrush current and is smooth and reliable. Since the commutation time is 0 milliseconds, the phase shifts by 120° only when the voltages of the two phases are equal; this constitutes natural commutation, resulting in no voltage spikes or inrush current.
3. Precisely control the phase-shifting switches to ensure segment-by-segment balance across all branches of the distribution network. A proprietary comprehensive algorithm for segment-by-segment voltage drop analysis accurately identifies the most unbalanced points on the lines and prioritizes adjustments to the phase-shifting switches closest to these points. This ensures optimal balance at every point along the lines and guarantees segment-by-segment balance across the entire network. It also more effectively reduces neutral current and improves end-point supply voltage.
4. It has no adverse effects on any type of electrical equipment. The zero-millisecond seamless phase-switching technology with constant voltage ensures no power interruptions or voltage sags, causing absolutely no disruption to users’ power supply; it provides stable and reliable phase switching for inductive, capacitive, and resistive loads alike.
5. Flexible functionality and parametric design. Phase-switching constraints can be configured. These constraints can be adjusted based on the specific conditions of each feeder, such as load factor, unbalance, and neutral current. The master controller supports multiple communication protocols for convenient management and monitoring. It communicates with phase-switching switches via LoRa wireless technology and can exchange data with other devices and backend systems through communication interfaces such as RS485 and GPRS. Tiered substation management facilitates large-scale deployment. Substation management follows a top-down hierarchical structure based on location, substation number, and equipment ID, ensuring clear and rapid identification during large-scale deployments.
6. Energy Conservation and Loss Reduction. Through the optimization of software and hardware technologies, the system offers excellent continuous control capabilities, which not only reduce transformer losses but also minimize line losses. By continuously adjusting the load phase throughout the day, the neutral line current is consistently kept at a minimum, resulting in significant reductions in losses and improvements in efficiency after commissioning.
7. Long commutation life: The commutation switch is guaranteed to withstand at least 200,000 commutation cycles. Once this threshold is exceeded, the switch will cease to function. The product can be returned to our company for replacement of the component, after which it can be put back into service.
8. The phase-switching device features an automatic bypass function. If a fuse blows, causing a power outage in the active phase, the device will automatically bypass the active phase to a live phase within less than 1 second. This ensures uninterrupted power supply to users and reduces customer complaints.
9. The phase-shifting unit features load identification. The main controller identifies the loads connected to the output terminals. If the load power factor is too low, the load power flow direction is negative, or the load current distortion rate exceeds the threshold, the phase-shifting protection device is prevented from operating normally.
10. Phase sequence verification: The phase-shifting unit includes a phase sequence verification function. If the phase sequences of the main controller and the phase-shifting unit do not match, phase shifting is prevented to ensure effective power quality improvement.
11. Data Acquisition Function: The main controller acquires data including three-phase line voltage, current, three-phase current imbalance, three-phase active power, reactive power, power factor, and frequency. The phase-shifting unit acquires data including three-phase line voltage, load voltage, load current, load active power, reactive power, power factor, frequency, and current distortion rate.
5500英文配图.png

Technical Parameters

Product NamePhase-Changing SwitchMaster Controller
Product ModelEM5500-PEXEM5500-BMC
Phase-Changing  Time0ms/
Phase-Changing MethodOn-load equal voltage 0 milliseconds seamless phase-changing/
Phase-Changing LifeNot less than 200,000 times (about 10 years)/
Communication Method230MHz LORA wireless communication, 433MHZ communication, RS485230MHz LORA wireless communication, GPRS, RS485
Uplink Data/Three-phase voltage, three-phase current, zero-line current, phase-changing event, alarm event, number of phase-changing, three-phase imbalance, load rate, power factor
Communication DistanceNo obstacles ≤4000 meters, between buildings ≤1500 metersNo obstacles ≤4000 meters, between buildings ≤1500 meters
Wiring MethodThree-phase four-wire Three-phase four-wire 
Interlocking MethodHardware differential pressure and signal differential interlocking; software verification latching/
Adjustment Method/Real-time current balance and power balance
Rated VoltageInterphase 380V±20%/single phase 220VInterphase 380V±20% single phase 220V
Rated Current120A0.05A; sampling CT: 5A
Rated Frequency50Hz, allowable deviation: ±5%50Hz, allowable deviation: ±5%
Voltage Measurement0.0V~264.0V;±0.5%0.0V~264.0V;±0.5%
Current Measurement0.0A~120.0A;±0.5%0.0A~5.0A;±0.5%
Active Power0.0kW~31.68kW;±1.0%0.0kW~1.32kW;±1.0%
Apparent Power0.0kVA~31.68kVA;±1.0%0.0kVA~1.32kVA;±1.0%
Reactive Power0.0kVar~31.68kVar;±1.0%0.0kVar~1.32kVar;±1.0%
Power Factor0.0~1.0;±1.0%0.0~1.0;±1.0%
Insulation Resistance≥100MΩ≥100MΩ
Overload Capacity2 times the rated current: 1 minute2 times the rated current: 1 minute
Withstand VoltagePower frequency 2.5kV, impact 5kVPower frequency 2.5kV, impact 5kV
Power Consumption≤2.5W≤2.5W
Installation MethodPole/wall hangingPole/wall hanging
Protection LevelIP54IP54
Use Environment-Indoor/outdoor, -40℃~85℃Indoor/outdoor, -40℃~85℃
Altitude≤2000 meters≤2000 meters
Weight3700g3574g
Dimensions485mm*227mm*109mm540mm*260mm*125mm