ETCR3480B Analog Insulation Resistance Tester
Main Features
Â
Suitable for insulation testing of high-voltage electrical equipment, including cables, transformers, power capacitors, and high-voltage switchgear.
Measuring Ranges: 0GΩ-400 GΩ
Insulation Resistance: +5% of scale length
Output Voltage: Temperature 23°C ± 5°C, humidity ≤ 70%, output voltage ± 10%
Power Source: 8 pcs of 1.5V SUM-3 battery or equivalent
Dimensions: 200(L)×140(W)×80(D)mm
Product Features
1. Suited for heavy duty electrical maintenance and servicing of industrial installations, cables, transformers, generators and switchgear where high voltage insulation tests are required.
2. Dual scales for low and high ranges which changes change automatically. Color coded scales for easy reading plus LED`s that illuminate in matching color.
3. Hard carrying case furnished as standard accessory. Houses both instrument and test leads in compact from. Made of plastic, it is highly water resistant.
4. Designed for low power consumption. Since the maximum current consumption is 90mA eight pieces of 1.5V SUM-3(or equipment) permit about 6 hours of continuo us operation even when the instrument in used on maximum load or twice longer minimum load.
5. The new type of meter with rechargeable battery has dual functions of AC and DC, and is equipped with a large capacity lithium battery. A professionally produced lithium battery charger with automatic protection for overvoltage and overcurrent charging. After being fully charged, the charger switches from a red light to a green light. No need to wait. Fast charging speed improves work efficiency.
Â
Technical Parameters
1.Measurement Range & Accuracy
|
DC Test voltage |
5000V |
10000V | |
|
Measuring Ranges |
0-5GΩ/2-200 GΩ (automatic change) |
0-10GΩ/4-400 GΩ (automatic change) |
|
|
Accuracy |
Insulation Resistance |
+5% of scale length |
+5% of scale length |
|
Output Voltage |
Temperature 23°C ± 5°C, humidity ≤ 70%, output voltage ± 10% | ||
2.Technical Specification
| Specification Name |
Parameters Description |
|
Operating Temperature & Humidity |
-10℃-+40℃ at 85% max. relative humidity |
|
Storage Temperature & Humidity |
-20℃-+60℃ at 90% max. relative humidity |
|
Insulation Resistance |
100M max./1000V between electrical circuit & housing case |
|
Withstand Voltage |
500V AC for one minute between electrical circuit & housing case |
|
Dimensions |
200(L)×140(W)×80(D)mm |
|
Weight |
Approx. 2kg (including batteries & line probe) |
|
Power  Source |
8 pcs of 1.5V SUM-3 battery or equivalent |
|
Accessories |
Hard Carrying Case, Batteries, Test Leads   (earth & guard leads) |