EM1000C/EM1000D/EM1010A/EM1010B Phase Sequence Meter
EM1000C Non-Contact Phase Sequence Indicator
Product Series : Phase Sequence Meter
Main Features :
Used for phase sequence detection (positive phase, reverse phase, phase loss), live wire inspection, simple power inspection, firewire identification, phase loss judgment, disconnection location search, line maintenance
Available Clamp Wire Diameter: Φ1.6mm ~ Φ16mm
Line Voltage: 70 ~ 1000V
Phase Sequence Status: Dynamic Sound And Light Indication
Product Introduction
EM1000C Non-Contact Phase Sequence Indicator also known as non-contact phase sequence meter, phase sequence detector, motor three-phase detector, phase sequence tester, motor steering tester, is used for phase sequence detection (positive phase, reverse phase, phase loss), live wire inspection, simple power inspection, firewire identification, phase loss judgment, disconnection location search, line maintenance.
The traditional phase sequence detection is that the terminals of the three-phase wires must be peeled off and the three exposed clips or test pins of the phase sequence meter must be connected to the three exposed firewires. The EM1000C adopts clamp-shaped non-contact inductive measurement. There is no need to peel off the wires and contact the high-voltage exposed firewire. The three super-inductive high-insulation clamps are directly clamped to the insulating skin of the three-phase firewire to detect the phase sequence, while sound and light indicate the positive or negative phase state of the phase sequence of the three-phase power supply.
EM1000C Non-Contact Phase Sequence Indicator has four powerful magnets attached to the back, which can be sucked and hung on the distribution box for use.Instrument detection is fast and convenient, and the display is clear at a glance, which greatly improves the safety of on-site testing, effectively protects the personal safety of operators, and increases productivity. It is an essential instrument for three-phase power supply phase sequence, motor testing, and circuit maintenance.
ETCRMETER is a high-end brand of ETCR. All products are manufactured by ETCR, which also provides technical support and after-sales service.
Product Features
1. Clamp-shaped non-contact inductive measurement is used. There is no need to peel off the outer skin of the cable and no need to contact the high-voltage exposed firewire. The phase sequence can be detected by directly clamping the three super-inductive high-insulation clamps on the insulated outer skin of the three-phase firewire.
2. Dynamic sound and light indicate the positive or negative phase state of the phase sequence of the three-phase power supply, which is clear at a glance.
3. The bottom plate of the instrument is equipped with 4 magnets. During the test, the instrument can be adsorbed on the metal shell of the equipment, which can withstand a weight of 800g, and the operation is convenient and handy.

Technical Parameters
| Specification Name | Parameters Description |
| Power Supply | DC 3V AA alkaline batteries (LR6)*2PCS |
| Live Power Range | AC70 ~ 1000V, 45 ~ 65Hz (Sine Wave Continuous Input) |
| Available Clamp Wire Diameter | external diameter Φ1.6mm ~ Φ16mm |
| LED Display | [Positive phase sequence] The phase detector lamp lights up clockwise [Negative phase sequence] The phase detector lamp lights up counterclockwise [Live power] L1, L2, L3 lamps light up in setting voltage range [Default phase] L1 or L2, or L3 lamp is not lighting [Open circuit] L1 or L2, or L3 lamp is not lighting |
| Buzzer | [Positive phase sequence] the buzzer sounds intermittently [Negative phase sequence] the buzzer sounds continuously |
| Battery Check | The POWER indication lamp light up after boot up; the LOW BATTERY lamp lightup when low battery |
| Auto Shutdown | 5 minutes after booting up, the meter automatically shutdown |
| Clamp Lead Length | 0.6m |
| Meter Dimension | 70mm x 75mm x 30mm |
| Weight | Instrument: 230g (include battery); |
| Max. Measure Voltage | AC 1000V |
| Insulation Strength | 5.4kV/rms |
| Max. Rated Power | 300mVA |
| Safety Standaerd | EN61010-1:2001, EN61010-031:2002, pollution level 2, CAT Ⅲ1000V, instantaneous overvoltage 6000V |
| Working Temperature & Humidity | – 10℃ ~ 55℃; below 80%RH |
| Store Temperature & Humidity | – 20℃ ~ 60℃; below 90%RH |
Model Comparison
| Product Model | Available Clamp Wire Diameter | Meter Dimension | Max. Measure Voltage | Max. Rated Power |
| Φ1.6mm~16mm | 70mm×75mm×30mm | AC 1000V | 300mVA |
| Φ10mm~40mm | 70mm×75mm×30mm | AC 1000V | 300mVA |