Menu

Earth Resistance Tester, Earth Resistance/Lightning Strike Current Online Detector, High Voltage Insulation Resistance Tester, High Voltage Electroscope/Approach Electric Alarm.......

  • Home |
  • Lightning Current/Earth Online Detector

Lightning Current/Earth Online Detector

EM2840 Series Lightning Current/Earth Online Detector

EM2840 Lightning Strike Current Online Detector
EM2840C Lightning Current/Earth Online Detector
EM2840T Lightning Current/Earth Online Detector

EM2840T Lightning Current/Earth Online Detector

 

Product Series : Lightning Current/Earth Online Detector

 

Main Features

 

SPD alarm action monitoring, including SPD alarm action time, lightning strike count, lightning current amplitude, earth resistance, earth current monitoring
Detector Structure: Separate type
Lightning Current CT Size: 120mm
Maximum Lightning Current Measurement Amplitude: 100KA
Minimum Lightning Current Measurement Amplitude: 2.5%FS
SPD Alarm Signal Monitoring Channels: 1
Earth Resistance Range: 0.01Ω~200Ω
Earth Current Range: AC 0.0mA~20A
RS485 Communication: Supports Modbus protocol
4G Communication (Optional)

Product Introduction

 

EM2840T  Lightning Current/Earth Online Detector is installed on the earth down lead, which can monitor SPD alarm actions and time, lightning strike counts and amplitude in real time and accurately. The SPD alarm function is suitable for SPD devices with dry contact output, which can timely and rapidly monitor SPD operation status. The detector also measures earth resistance and earth current in real time.
EM2840T Lightning Current/Earth Online Detector consists of controller, sensor and mounting hardware. EM2700T monitor is integrated structure with combined sensor and controller. The detector has RS485 communication interface (supports MODBUS‑RTU protocol) or optional 4G communication module (supports MQTT protocol) and realizes remote online monitoring by upper computer software or background system. Users can use our company’s RS485 earth resistance online monitoring upper computer software or 4G wireless earth resistance online monitoring background to realize remote real‑time monitoring of earth conditions. 
ETCRMETER is a high-end brand of ETCR. All products are manufactured by ETCR, which also provides technical support and after-sales service.

Product Features
1. The detector can monitor and collect SPD alarm signals.
2. Monitors earth resistance, earth current, and amplitude, polarity and occurrence time of lightning current.
3. Equipped with display screen for real‑time observation of measured earth resistance and earth current values.
4. With RS485 communication or 4G communication(optional) to realize remote monitoring.
5. The sensor housing is made of 304 stainless steel, making it sturdy, durable, impact-resistant, and resistant to high and low temperatures for all-weather use.
EM2840T (7).jpg EM2840T (8).jpg

Technical Parameters

Specification NameParameters Description
FunctionsSPD alarm action monitoring, including SPD alarm action time, lightning strike count, lightning current amplitude, earth resistance, earth current monitoring
Power SupplyDC 9V~24V external power supply
Display Screen47mm × 28.5mm
Earth Resistance MeasurementRange: 0.01Ω~200Ω
Resolution: 0.001Ω
Accuracy: ± 2%rdg ± 3dgt
Earth Current MeasurementRange: AC 0.0mA~20A
Resolution: 0.1mA
Accuracy: ± 2%rdg ± 5dgt
Lightning Current MeasurementMax. measurement amplitude: 100kA(Customizable)
Min. measurement amplitude: 2.5%FS
Accuracy: ±(10%rdg+1 %*Fs)
SPD Alarm Channel1
Alarm TimeYear, Month, Day, Hour, Minute, Second
Communication ModeRS485 (Supports Modbus Protocol), 4G (Optional)
Upload DataLightning strikes counts, Lightning amplitude and time, Earth resistance value, Earth current value
ShiftFully Automatic shifting
Overflow IndicationWhen resistance value > 200Ω; current value > 20A, display “OL” symbol.
Power and Communication Cable Wiring Labels

Red—Power input positive;
Black—Power input ground;
Green—RS485 signal positive;
Yellow—RS485 signal negative;
White—Shielding ground; (power input ground and shielding ground can be short-circuit connection)

Network Count

Wired network: 1 ~ 250 earth points, expandable

Wireless network: 60,000 earth points, expandable
Communication Distance

Wired network: Approx. 1000 meters, expandable

Wireless network: Unlimited
Alarm IndicationAudible & visual alarm and LCD display
Alarm SettingSetting with panel buttons, background setting
Sensor Opening Size53mm x 20mm
Earth Interference CurrentAvoid
Single Measurement TimeApprox. 0.5s
Working Current12VDC 50mA Max. (12VDC 150mA Max. for 4G version)
Protection LevelIP66
Monitor Dimensions

Controller: 118mm x 112mm x 46mm

Sensor: 119mm x 75mm x 109mm

WeightApprox. 1275g
Working Temperature & Humidity– 20℃~55℃;20ï¼…RH~90ï¼…RH